The HD is installed on the return line from the solar
collector(s). When the temperature in the storage tank
exceeds the pre-set limit (~80oC
/ 176oF), the controller
switches a solenoid which directs the solar return flow
through the HD before returning it back into the standard
flow line. Alternatively a thermostatic mixing valve/tempering
valve set to a suitable temperature can be used, providing
mechanic, automatic regulation of flow through the heat
dissipator.
As the hot water passes through the HD, heat is dissipated
via the aluminium fins to surrounding air, the vertical
fin arrangement promoting a passsive air current.
One HD-25 unit can dissipate 100% of the heat produced
by an AP-30 collector in
full sun, during very high ambient temperatures.
The copper pipe to and from the collector should be heavily
insulated, as should the lengths of pipe to and from the
HD. The solenoid valve prevents flow of collector return
water through the HD during normal temperature operation,
thus preventing unnecessary heat loss.